TRANSFORMERS FOR MEDICAL LOCATIONS

Transformers for medical locations

Power up to 10KVA

Braga Trasformatori has decades of experience in manufacturing transformers in accordance with the European Standard IEC 61558-2-15 for the power supply of medical locations.

These are isolation transformers, single-phase or three-phase, intended for Group 2 medical locations, designed to form the IT system on the secondary side, with a nominal primary voltage not exceeding 1 kV AC and a nominal frequency not exceeding 500 Hz.

Typical applications requested by our customers include:

  • Operating theatres and intervention areas.
  • Intensive care and resuscitation units.

The rated power of these transformers — which we build to the highest safety and testing standards given their intended environment — ranges from 500 VA to 10 kVA.

Braga Trasformatori can manufacture any intermediate power step required by the customer, both in batches and as single units.

Main construction features

  • Double or reinforced insulation.
  • Electrostatic shield between windings to reduce disturbances and contribute to protection.
  • Impregnation and insulating materials to improve thermal dissipation and long-term reliability.
  • Designed for continuous operation with low noise, suitable for sensitive environments.
  • Thermal protection: on request, temperature sensors (e.g. PT100) or thermal contacts.
  • Powers, voltages and configurations on request.
  • Integration into existing panels as specified by the customer (terminal blocks, vertical/horizontal arrangement, etc.).
  • Optional enclosure supply for installations requiring a higher degree of protection.

Why special construction is essential in medical environments

  • Patient and operator safety. Galvanic separation and the electrostatic shield reduce network disturbances that could interfere with critical equipment.
  • Service continuity. In environments where an interruption may have clinical impacts, the power supply must remain stable, reliable and monitored.
  • Disturbance reduction. Filtering of surges and transients from the network improves the reliability of electromedical equipment and imaging systems.

Specific requirements for Group 2 medical locations

Medical locations are classified into groups based on risk and the invasiveness of procedures. Group 2 includes operating theatres and intensive care areas where intracardiac applications are possible. In these environments it is required to use:

  • An IT-M system on the secondary of the isolation transformer to ensure continuity even in the presence of the first earth fault.
  • Insulation monitoring of the circuit via a dedicated device with audible/visual indications.
  • An equipotential bonding network and proper coordination of protective devices in accordance with current installation standards.

Given the safety requirements, it is essential to rely on an experienced manufacturer that designs and builds in Italy with the best materials; for this reason, Braga Trasformatori is the preferred partner for many industry operators.


Technical characteristicsValue
Reference standardsIEC 61558-1, IEC 61558-2-15
Thermal insulation classF
Reference ambient temperature40° C
Protection degreeIP00
Suitable for installation up toIP2x
TestsAccording to standards
ConnectionsTerminal block
TerminalsNon-flammable Nylon